Model 9119-590, 9406-595, and 9119-595 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

The IBM® eServer™ i5 and eServer p5 model 590 and 595 consist of multiple components, as summarized in the following table.

Table 1. Model 9119-590, 9406-595, and 9119-595 components
Model Description Minimum per system Maximum per system
FC6251 (9119-590, 9119-595, 9406-595) Slimline door set for primary rack (front and rear) See Doors and covers. 1 1
FC6252 (9119-590, 9119-595, 9406-595) Acoustic door set for primary rack (front and rear) See Doors and covers. 1 1
FC8691 (9119-590, 9119-595)

Optional expansion frame

(Based on number of I/O and switch drawers installed.)

0 1
FC8294 ( 9406-595)

Optional base 1.8 m rack

0 1
FC6253 (9119-590, 9119-595) Slimline door set for 8691 (front and rear) 0 1
FC6254 (9119-590, 9119-595) Acoustical door set for 8691 (front and rear) 0 1
9119-595 (FC8970) 16-way, 2.1 GHz processor book 110 4
9119-595 and 9406-595 (FC8968) 16-way, 2.3 GHz processor book 110 4
9119-590 (FC8967) 16-way, 2.1 GHz processor book 110 2
9406-595 (FC8966) 16-way, 1.9 GHz processor book 110 4
9406-595 (FC8981) 16-way, 1.65 GHz processor book 110 4
9119-590 (FC7981) 16-way, 1.9 GHz processor book 110 2
9119-595 (FC7813) 16-way, 1.9 GHz processor book 110 4
9119-595 (FC8969) 16-way, 1.9 GHz processor book    
9119-595 (FC7988) 16-way, 1.65 GHz processor book 110 4
FC5792 (9119-595) Optional base rack. See Planning for 5792 base rack.    
Various Hardware Management Console (HMC)6 04 24

7040-61D

5791 (9119-590, 9119-595)

5794 (9119-590, 9119-595)

Optional I/O drawer (20 PCI cards max., 16 disk drives maximum)

0 (9406)

1 (9119)

8-way or 16-way: 6 drawers maximum1

32-way: 12 drawers maximum2

48-way and 64-way: 4 drawers maximum3

9406-5959

FC6200 or FC6201 (9119-590, 9119-595) Optional integrated battery backup feature 0 6
FC3757 (9119-590, 9119-595, 9406-595) Service Shelf Tool Kit8 1 1
FC9194 ( 9406-595) Base PCI-X Expansion tower (shipped with a 9406-595) 1 1
Note:
  1. For the 9119-590 and 9119-595, the 16-way processor configuration supports up to 6 I/O drawers.
  2. For the 9119-590 and 9119-595, the 32-way processor configurations support up to 12 I/O drawers.
  3. For the 9119-590 and 9119-595, the 48-way and 64-way processor configurations support a maximum of 12 I/O drawers, which require a FC5792 frame.
  4. An HMC can connect to multiple systems (therefore, an HMC may not need to be ordered), or up to two HMCs can connect to the system for redundancy.
  5. For the 9119-590 and 9119-595, the The 32-way, 48-way, and 64-way processor configurations are based on the combining of multiple 16-way processors. The 8-way processor configuration is a 16-way with eight processors available for upgrade on demand.
  6. For the model 590 and 595, a Hardware Management Console must be provided within the same room and within 8 m (26 ft.) of the server. Or, as an alternative to the local HMC requirement, it is acceptable for you to provide a supported device (such as, a PC), with connectivity and authority to operate through a remotely-attached HMC. This local device must be in the same room and within 8 m (26 ft.) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the server.
  7. The 32-way processor configuration of the 9119-590 supports a maximum of eight I/O drawers.
  8. The FC3757 Service Shelf Tool Kit contains six separate tool kits that are required for the installation and maintenance of the 9119-590, 9119-595 and 9406-595 processor books and memory cards. Each kit weighs ≤ 40 lb. Without this feature, installation and maintenance may be delayed. At least one FC3757 is required on site where one or more model 590 or 595 are located.
  9. A number 4643 indicates that a 7040-61D I/O drawer is installed in the 24-inch primary rack of a model 9406-595. One to four 4643s may be installed. Only AIX® and Linux operating system supported I/O features may be installed in the 7040-61D. Other iSeries® I/O towers or drawers may be attached via HSL/RIO loops.
  10. Minimum per system is based on one processor with this feature code. Processor feature codes cannot be mixed.
Table 2. Server specifications
Specifications for model 9119-590, 9406-595, and 9119-59514

Plan views

Top down view

ASHRAE declarations (heat load data for various configurations)

Dimensions and weight8
Physical characteristic Slimline doors1 Acoustical doors1
  1 Frame 2 Frames 1 Frame 2 Frames
Height 2025 mm (79.7 in.) 2025 mm (79.7 in.) 2025 mm (79.7 in.) 2025 mm (79.7 in.)
Width 785 mm (30.9 in.) 1575 mm (62.0 in.) 785 mm (30.9 in.) 1575 mm (62.0 in.)
Depth 1326 mm (52.2 in.) 1326 mm (52.2 in.) 1681 mm (66.2 in.) 1681 mm (66.2 in.)
Weight10 - model 9119-595 maximum configuration
  With integrated battery backup and slimline doors Without integrated battery backup with slimline doors With integrated battery backup and with acoustical doors Without integrated battery backup and with acoustical doors
Single frame 1419 kg (3128 lb.) 1358 kg (2995 lb.) 1427 (3147 lb.) 1367 kg (3014 lb.)
Double frame 2441 kg (5381 lb.) 2381 kg (5249 lb.) 2458 (5420 lb.) 2398 (5287 lb.)
Weight10 - model 9406-595 configuration (Weight does not include the required I/O tower. See the 9194 I/O expansion unit specification sheet for more details)
  Without integrated battery backup with slimline doors Without integrated battery backup and with acoustical doors
Single frame12, 13 1358 kg (2995 lb.) 1367 kg (3014 lb.)
Weight10 - model 9119-590 maximum configuration
  With integrated battery backup and with slimline doors Without integrated battery backup and with slimline doors With integrated battery backup and with acoustical doors Without integrated battery backup and with acoustical doors
Single frame 1419 kg (3128 lb.) 1358 kg (2995 lb.) 1427 kg (3147 lb.) 1367 kg (3014 lb.)
Double frame 2230 kg (4917 lb.) 1960 kg (4321 lb.) 2248 kg (4956 lb.) 1977 kg (4359 lb.)
Shipping dimensions and weight9
Height 2311 mm (91 in.)
Width 940 mm (37 in.)
Depth 1511 mm (59.5 in.)
Weight Varies by configuration
Electrical and thermal characteristics (3-phase) - 9119-590, 9119-595 - for additional information, see Total system power consumption
Rated voltage and frequency (3 phase) 200 to 240 V ac at 50 to 60 Hz 380 to 415 V ac at 50 to 60 Hz 480 V ac at 50 to 60 Hz
Rated current, power cord with 100 A plug FC 8686 or 8687 (amps per phase) 60 32 24
Rated current, power cord with 60 A plug, FC 8688 or 8689 (amps per phase) 48 – – – –
Rated current, all other power cords (amps per phase) 60 32 24
Maximum power (1.9 GHz , 2.1 GHz, and 2.3 GHz processors) 22.7 kW
Maximum power (1.65 GHz processor) 20.3 kW
Power factor 0.99 0.99 0.99
Inrush current (maximum)3 163 A
Thermal output (maximum for 1.9 GHz , 2.1 GHz, and 2.3 GHz processors) 77.5 kBtu/hr 77.5 kBtu/hr 77.5 kBtu/hr
Thermal output (maximum for 1.65 GHz processor) 69.3 kBtu/hr 69.3 kBtu/hr 69.3 kBtu/hr
Electrical and thermal characteristics (3-phase) - 9406-595 - for additional information, see Total system power consumption
Rated voltage and frequency (single phase) 200 to 240 V ac at 50 to 60 Hz 380 to 415 V ac at 50 to 60 Hz 480 V ac at 50 to 60 Hz
Rated current, power cord with 100 A plug FC 8686 or 8687 (amps per phase) 60 32 24
Rated current, power cord with 60 A plug, FC 8688 or 8689 (amps per phase) 48 – – – –
Rated current, all 60 32 24
Maximum power (1.65 GHz processor) 19.4 kW
Power factor 0.99 0.97 0.93
Inrush current (maximum)3 163 A
Thermal output (maximum for 1.65 GHz processor) 66.2 kBtu/hr 66.2 kBtu/hr 66.2 kBtu/hr
Phase 9406-595, 9119-595, 9119-590 3
Dual power feature code Standard7
Branch circuit breaker and cord information See Breaker rating and cord information
Power cord length

4.2 m (14 ft.) - all locations (except Chicago)

1.8 m (6 ft.) - United States (Chicago)

Environment specifications
Recommended operating temperature5 (16-way, 32-way) 10 degrees to 32 degrees C (50 degrees to 89.6 degrees F)
Recommended operating temperature5 (48-way and 64-way) 10 degrees to 28 degrees C (50 degrees to 82.4 degrees F)
Nonoperating temperature (All models) 10 degrees to 43 degrees C (50 degrees to 109.4 degrees F)
Storage temperature (All models) 1 degree to 60 degrees C (33.8 degrees to 140 degrees F)
Shipping temperature (All models) -40 degrees to 60 degrees C (-40 degrees to 140 degrees F)
Operating Nonoperating Storage4 Shipping4
Maximum wet bulb 23 degrees C (73.4 degrees F) 23 degrees C (73.4 degrees F) 27 degrees C (80.6 degrees F) 29 degrees C (84.2 degrees F)
Noncondensing relative humidity 8 to 80 % 8 to 80 % 5 to 80 % 5 to 100 %
Maximum altitude (operating)

8-way, 16-way, 32-way - 3048 m (10000 ft.)

48-way, 64-way - 2133 m (7000 ft.)

Acoustical noise emissions6, 15
Product configuration LWAd (Bels)6 LpAM (dB)6 (bystander, 1 m)
Operating Idle Operating Idle
Typical configuration with two processors, two I/O drawers, and bulk power unit; acoustical door set 7.6 7.6 59 59
Typical configuration with two processors, two I/O drawers, and bulk power unit; slimline door set 8.3 8.3 65 65
Maximum configuration with four processors, four I/O drawers, and bulk power unit; acoustical door set 7.9 7.9 61 61
Maximum configuration with four processors, four I/O drawers, and bulk power unit; slimline door set 8.611 8.611 6811 6811
Service clearances
For a graphical representation of service clearances, see Service clearances
Seismic considerations: See Secure the rack
Data communications
Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law
Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950-1; CAN/CSA C22.2 No. 60950-1; EN 60950-1; IEC 60950-1 including all national differences
Note:
  1. Doors are not installed during product shipment to the customer.
  2. Refer to Approximate system weights by configuration for the approximate weight of your system configuration.
  3. Inrush currents occur only at initial application of power (short duration for charging capacitors). No inrush currents occur during the normal power off-on cycle.
  4. When an IBM-approved vapor bag and desiccant packets are used to protect the system, the storage specifications are valid for 6 months and the shipping specifications are valid for 1 month. Otherwise, storage and shipping specifications are valid for two weeks each.
  5. For the 8-way, 16-way, and 32-way processor configurations, the upper limit of the dry bulb temperature must be derated 1 degree C (1.8 degrees F) per 219 m (719 ft.) above 1295 m (4250 ft.). Maximum altitude is 3048 m (10000 ft.). For the 48-way and 64-way configurations, the upper limit of the dry bulb temperature must be derated 1 degree C (1.8 degrees F) per 210 m (688 ft.) above 1295 m (4250 ft.). Maximum altitude is 2133 m (7000 ft.).
  6. LWAd is the upper-limit A-weighted sound level; LpAM is the mean A-weighted sound pressure measured at the 1-meter bystander postions; 1 B = 10 dB.
  7. Dual power and power cords are standard on the Model 9119-590, 9406-595, and 9119-595. For maximum availability, each of the power cords should be fed from independent power grids.
  8. For specific configuration weights, see Approximate system weights by configuration. The feature code 7960 (Compact Handling Option) allows the processor or expansion frame to pass through doors that are less than 2.0 m (79.5 in.). The top 8U section of the frame, including the power subsystem, is removed at the factory and shipped separately for installation at the customer location. The height of the rack with the upper section removed is approximately 1.65 m (65 in.).
  9. Shipping dimensions are indicated for each frame. Each frame is shipped separately.
  10. See Approximate system weights by configuration for detailed information on weights based on configuration.
  11. Attention: Your server installation may be subject to government regulations (such as those prescribed by OSHA or European Community Directives that cover noise level exposure in the workplace. The model 9119-590, 9119-595, and 9406-595 is available with an optional acoustical door feature that can reduce the likelihood of exceeding noise level exposure limits for densely populated racks. The actual sound pressure levels in your installation will depend on a variety of factors, including the number of racks in the installation; the size, materials, and configuration of the room where the racks are installed; the noise levels from other equipment; the room ambient temperature, and employees' location in relation to the equipment. It is recommended that a qualified person, such as an industrial hygienist, be consulted to determine whether the sound pressure levels to which employees may be exposed exceed regulatory limits.
  12. The 9406-595 has a maximum of four 7040-61D 24-inch I/O drawers in the primary processor rack. It does not support a double or secondary rack
  13. The 9406-595 does not support internal battery backup.
  14. The cabling requirements of the model 595 limit the distance between the server frame and a separately powered I/O frame. See Special requirements for model 595 cabling for details.
  15. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

To effectively plan for the model 9119-590, 9406-595, and 9119-595, the following topics are also provided.