Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.
Use the following specifications to plan for your server.
Plan views |
Pictured is the model 9406-570, and 9117-570 server. Figure 1. Model 9406-570, and 9117-570 server
|
||||
Dimensions | Width | Depth | Height | EIA units1 | Weight |
Metric | 483 mm | 790 mm | 174.1 mm | 4 | 63.6 kg |
English | 19 in. | 31.1 in. | 6.85 in. | 140 lb. | |
Rack-mounted drawer | |||||
Shipping Dimensions | Width | Depth | Height | Weight | |
Metric | 648 mm | 991 mm | 704 mm | 80 kg | |
English | 25.5 in. | 39 in. | 27.7 in. | 175 lb. | |
Rack-mounted drawer (China) | |||||
Shipping Dimensions | Width | Depth | Height | Weight | |
Metric | 640 mm | 965 mm | 692 mm | 80 kg | |
English | 25.2 in. | 38 in. | 27.25 in. | 175 lb. | |
Drawer mounted in 0551 rack, 7014-T00 , 7014-T42, 0553, 0555 racks, Power distribution unit (PDU) |
0231 (9117-570, 4-way), 0232 (9117-570, 8-way), 0241 (9117-570, 12-way), 0242 (9117-570, 16-way) 0260 (9116-561, 8-way) 0261 (9116-561, 16-way) |
||||
Electrical | |||||
kVA (maximum) | 1.368 | ||||
Rated voltage and frequency6 | 200-240V ac at 50/60 plus or minus 0.5 Hz | ||||
Thermal output (maximum)9 | 4437 Btu/hr | ||||
Maximum power consumption4, 7 | 1300 W | ||||
Power factor | 0.95 | ||||
Inrush current (maximum) | 88 A | ||||
Leakage current (maximum) | 3 mA | ||||
Phase | 1 | ||||
Compatible plug types | 2, 5, 6, 10, 18, 19, 22, 23, 24, 25, 26,32, 34, 62, 64, 66, 69 | ||||
Dual power feature code | Included | ||||
Branch circuit breaker | 20 A maximum | ||||
Power cord length | 2.7 m (9 ft.) Europe; 1.8 m (6 ft.) U.S.; 1.8 m (6 ft.) and 4.3 m (14 ft.) for U.S. cords with plug type 5 | ||||
Environment requirements | |||||
Recommended operating temperature | 5 degrees to 35 degrees C (41 degrees to 95 degrees F) | ||||
Nonoperating temperature | 5 degrees to 40 degrees C (41 degrees to 104 degrees F) | ||||
Shipping temperature | -40 degrees to 60 degrees C (-40 degrees to 140 degrees F) | ||||
Operating | Nonoperating | ||||
Wet bulb temperature | 23 degrees C (73.4 degrees F) | 27 degrees C (80.6 degrees F) | |||
Noncondensing humidity | 8 to 80% | 8 to 80% (5 to 100% – shipping) | |||
Maximum altitude | 3048 m (10000 ft.) | 3048 m (10000 ft.) | |||
Noise emissions2, 8 | |||||
Product description | Declared A-weighted sound power level, LWad (B) | Declared A-weighted sound pressure level, LpAm (dB) | |||
Operating | Idle | Operating | Idle | ||
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 4-way configuration with four hard drives and two power supplies | 6.8 | 6.8 | 533 | 533 | |
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 4-way configuration with four hard drives and two power supplies and acoustic doors (feature code 6248 or 6249) | 6.23 | 6.23 | 463 | 463 | |
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 16-way configuration with four hard drives and two power supplies | 7.4 | 7.3 | 59 | 59 | |
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 4-way configuration with four hard drives and two power supplies and acoustic doors (feature code 6248 or 6249) | 6.83 | 6.73 | 533 | 533 | |
Service clearances | |||||
Clearances | Front | Back | Left or right | Top | |
Operating | 762 mm (30 in.) | 762 mm (30 in.) | |||
Nonoperating | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | |
Seismic considerations: | |||||
Data communications: | |||||
Electromagnetic compatibility compliance: FCC Part 15, ICES-003 | |||||
Safety compliance: IEC 60950; UL 60950; CSA 60950 | |||||
Note:
|
When the server is managed by a Hardware Management Console (HMC), the console must be provided within the same room and within 8 m (26 ft.) of the server.
You must prepare your environment to accept the new product based on the installation planning information provided, with assistance from an IBM Installation Planning Representative (IPR) or IBM authorized service provider. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The IBM authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.