Model 9406-570, 9117-570, and 9116-561 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Server specifications

Plan views

Top down view

ASHRAE declarations

Pictured is the model 9406-570, and 9117-570 server.

Figure 1. Model 9406-570, and 9117-570 server
9406-570 and 9117-570 server
Dimensions Width Depth Height EIA units1 Weight
Metric 483 mm 790 mm 174.1 mm 4 63.6 kg
English 19 in. 31.1 in. 6.85 in. 140 lb.
Rack-mounted drawer
Shipping Dimensions Width Depth Height Weight
Metric 648 mm 991 mm 704 mm 80 kg
English 25.5 in. 39 in. 27.7 in. 175 lb.
Rack-mounted drawer (China)
Shipping Dimensions Width Depth Height Weight
Metric 640 mm 965 mm 692 mm 80 kg
English 25.2 in. 38 in. 27.25 in. 175 lb.

Drawer mounted in 0551 rack, 7014-T00 , 7014-T42, 0553, Start of change0555End of change racks, Power distribution unit (PDU)

0231 (9117-570, 4-way),

0232 (9117-570, 8-way),

0241 (9117-570, 12-way),

0242 (9117-570, 16-way)

0260 (9116-561, 8-way)

0261 (9116-561, 16-way)

Electrical
kVA (maximum) 1.368
Rated voltage and frequency6 200-240V ac at 50/60 plus or minus 0.5 Hz
Thermal output (maximum)9 4437 Btu/hr
Maximum power consumption4, 7 1300 W
Power factor 0.95
Inrush current (maximum) 88 A
Leakage current (maximum) 3 mA
Phase 1
Compatible plug types 2, 5, 6, 10, 18, 19, 22, 23, 24, 25, 26,32, 34, 62, 64, 66, 69
Dual power feature code Included
Branch circuit breaker 20 A maximum
Power cord length 2.7 m (9 ft.) Europe; 1.8 m (6 ft.) U.S.; 1.8 m (6 ft.) and 4.3 m (14 ft.) for U.S. cords with plug type 5
Environment requirements
Recommended operating temperature 5 degrees to 35 degrees C (41 degrees to 95 degrees F)
Nonoperating temperature 5 degrees to 40 degrees C (41 degrees to 104 degrees F)
Shipping temperature -40 degrees to 60 degrees C (-40 degrees to 140 degrees F)
Operating Nonoperating
Wet bulb temperature 23 degrees C (73.4 degrees F) 27 degrees C (80.6 degrees F)
Noncondensing humidity 8 to 80% 8 to 80% (5 to 100% – shipping)
Maximum altitude 3048 m (10000 ft.) 3048 m (10000 ft.)
Noise emissions2, 8
Product description Declared A-weighted sound power level, LWad (B) Declared A-weighted sound pressure level, LpAm (dB)
Operating Idle Operating Idle
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 4-way configuration with four hard drives and two power supplies 6.8 6.8 533 533
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 4-way configuration with four hard drives and two power supplies and acoustic doors (feature code 6248 or 6249) 6.23 6.23 463 463
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 16-way configuration with four hard drives and two power supplies 7.4 7.3 59 59
9406-570, 9117-570, and 9116-561, 1.65 and 1.9 GHz, 4-way configuration with four hard drives and two power supplies and acoustic doors (feature code 6248 or 6249) 6.83 6.73 533 533
Service clearances
Clearances Front Back Left or right Top
Operating 762 mm (30 in.) 762 mm (30 in.)    
Nonoperating 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.)
Seismic considerations:
Data communications:
Electromagnetic compatibility compliance: FCC Part 15, ICES-003
Safety compliance: IEC 60950; UL 60950; CSA 60950
Note:
  1. See 0551, 0553, 7014, or Start of change0555End of change rack configurations for typical configurations when the 0551, 0553, 7014, or Start of change0555End of change rack is populated with various server models.
  2. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.
  3. Estimated value
  4. Maximum power consumption is specified for each 9117-570 4-way drawer. The 8-way, 12-way, and 16-way configurations are based on the use of multiple 4-way drawers (for example, an 8-way configuration consists of two 4-way drawers, a 12-way configuration consists of three 4-way drawers, and a 16-way configuration consists of four 4-way drawers).
  5. All Model 570 disk bays should be filled when the unit is shipped from IBM® with either disk drives or slot fillers, but if a disk is removed, refill the disk slot with either another disk drive or a disk slot filler. Filling the disk drive slot will help ensure proper airflow for cooling and help maintain optimal EMI compliance. Ordering feature 6598 results in four additional disk slot fillers being shipped.
  6. The power supplies automatically accept any voltage with the published, rated-voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  7. Maximum power consumption is specified for each 9116-561 8-way drawer. The 8-way and 16-way configurations are based on the use of multiple 8-way drawers (for example, a 16-way configuration consists of two 8-way drawers).
  8. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
  9. Thermal output value is for each 4-way drawer configuration.

Special Hardware Management Console considerations

When the server is managed by a Hardware Management Console (HMC), the console must be provided within the same room and within 8 m (26 ft.) of the server.

Note: As an alternative to the local HMC requirement, it is acceptable for you to provide a supported device, such as a PC, with connectivity and authority to operate through a remotely attached HMC. This local device must be in the same room and within 8 m (26 ft.) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the system.

Delivery and subsequent transportation of the equipment

DANGER
Heavy equipment—personal injury or equipment damage might result if mishandled. (D006)

You must prepare your environment to accept the new product based on the installation planning information provided, with assistance from an IBM Installation Planning Representative (IPR) or IBM authorized service provider. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The IBM authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.